      Medical gas pipeline system disruption during tropical cyclone 'Fani' – a clear and present danger of tropical cyclones: Are we prepared?

      letter

      Read this article at

      Bookmark
          There is no author summary for this article yet. Authors can add summaries to their articles on ScienceOpen to make them more accessible to a non-specialist audience.

          Abstract

          Sir, The sudden disruption of oxygen supplies due to damage to medical gas pipeline system (MGPS) during a natural disaster can adversely affect patient safety during anaesthesia. With the alarming climate change crisis, we are vulnerable to increasing frequency and severity of natural disasters such as tropical cyclones in recent years. Here, we present such a life-threatening disaster which occurred during the category five cyclonic storm Fani. On 3rd May 2019, it made landfall in the state of Odisha, India with a wind speed of more than 250 kmph creating huge devastation.[1] Anticipating any untoward event during the cyclone, the routine surgeries were deferred. However, emergency surgeries were going on. Suddenly oxygen failure alarm started ringing in the panel and the central oxygen pipeline pressure decreased to zero. The type E oxygen cylinders which were present behind the workstation were opened and the surgeries were completed uneventfully. We were informed that all the medical gas pipelines (air, oxygen, nitrous, vacuum) were disrupted as part of the chimney of the boiler unit broke during strong wind and fell down on the MGPS at its outlet near the gas manifold [Figure 1]. Figure 1 The broken medical gas pipelines (blue arrow) at its outlet from the medical gas manifold. The broken chimney of the boiler unit (white arrow). Left top inset: The broken part of the chimney of the boiler which fell over the medical gas pipelines during the cyclone. Right bottom inset: Medical gases pipelines inside the manifold The standards while installing the MGPS system was not properly followed as found post-disaster. As a lesson learnt, we would like to highlight the concerns and safety measures which should be taken to preventing damage to the MGPS during such a disaster. Adequate experience and knowledge of medical administration and the involved department (anaesthesia and critical care) while installing the MGPS is one of the important factors which should be taken into account while installing the MGPS and liquid oxygen plant Pipelines in exposed areas shall be protected from physical damage Medical gas piping must be clearly identified using non removable stickers that are colour coded according to the gas Figure 1] Hangers should be installed as required for support of all exposed pipings MM Kembla Kemlag sheaths are available to fit over and protect. There are 12.7 mm (1/2”) and 19.05 mm (3/4”) size copper tubes through which the pipelines pass as they traverse masonry walls, partitions or floors[2] Pipelines are preferred to be buried in cyclone-prone areas. Buried gas pipelines are preferred to avoid physical damage to them due to high-speed winds If buried then a sticker must be present over the ground to identify them Buried pipelines shall be protected adequately against frost, corrosion and physical damage Copper tubes may experience severe corrosion if buried in direct contact with extreme environments Medical gas pipelines may be placed in the same tunnel, trench or duct with fuel gas pipelines or steam lines, provided that these medical gas pipelines are a minimum of 50 mm from other pipeline systems and combustible material and there is good ventilation Medical gas pipelines should not be enclosed in reinforced concrete or placed under slab on ground floors. Adequate stocks of oxygen cylinders should be available for two days in the manifold Specifications must be followed and certified from competent authority or experts Maintenance should be carried out at regular intervals and any damage should be repaired.[3] Natural disasters are unavoidable. With climate change, such disasters are going to increase in future. We should take appropriate measures to protect MGPS to prevent damage during such disasters and be prepared to manage any unanticipated events. Financial support and sponsorship Nil. Conflicts of interest There are no conflicts of interest.

          Related collections

          Most cited references2

          • Record: found
          • Abstract: not found
          • Article: not found

          Seconds from disaster-crisis in critical care unit during tropical cyclone ‘Fani’

            Bookmark
            • Record: found
            • Abstract: not found
            • Book: not found

            Medical gas pipeline system

              Bookmark

              Author and article information

              Journal
              Indian J Anaesth
              Indian J Anaesth
              IJA
              Indian Journal of Anaesthesia
              Wolters Kluwer - Medknow (India )
              0019-5049
              0976-2817
              May 2020
              01 May 2020
              : 64
              : 5
              : 439-441
              Affiliations
              [1]Department of Trauma and Emergency, All India Institute of Medical Sciences, Bhubaneswar, Odisha, India
              [1 ]Department of Anaesthesia and Critical Care, All India Institute of Medical Sciences, Bhubaneswar, Odisha, India
              Author notes
              Address for correspondence: Dr. Chitta R Mohanty, Department of Trauma and Emergency, All India Institute of Medical Sciences, Bhubaneswar - 751 019, Odisha, India. E-mail: tem_chitta@ 123456aiimsbhubaneswar.edu.in
              Article
              IJA-64-439
              10.4103/ija.IJA_67_20
              7286392
              32724258
              2f2042fd-5a60-469a-8ccb-cf558721625d
              Copyright: © 2020 Indian Journal of Anaesthesia

              This is an open access journal, and articles are distributed under the terms of the Creative Commons Attribution-NonCommercial-ShareAlike 4.0 License, which allows others to remix, tweak, and build upon the work non-commercially, as long as appropriate credit is given and the new creations are licensed under the identical terms.

              History
              : 19 January 2020
              : 13 February 2020
              : 29 February 2020
              Categories
              Letter to Editor

              Anesthesiology & Pain management
              Anesthesiology & Pain management

              Comments

              Comment on this article