      Immediate and delayed responses of power lines and transformers in the Czech electric power grid to geomagnetic storms

      Preprint

      Read this article at

      Bookmark
          There is no author summary for this article yet. Authors can add summaries to their articles on ScienceOpen to make them more accessible to a non-specialist audience.

          Abstract

          Eruptive events of solar activity often trigger abrupt variations of the geomagnetic field. Through the induction of electric currents, human infrastructures are also affected, namely the equipment of electric power transmission networks. It was shown in past studies that the rate of power-grid anomalies may increase after an exposure to strong geomagnetically induced currents. We search for a rapid response of devices in the Czech electric distribution grid to disturbed days of high geomagnetic activity. Such disturbed days are described either by the cumulative storm-time \(Dst\) or \(d(\textit{SYM-H})/dt\) low-latitude indices mainly influenced by ring current variations, by the cumulative \(AE\) high-latitude index measuring substorm-related auroral current variations, or by the cumulative \(ap\) mid-latitude index measuring both ring and auroral current variations. We use superposed epoch analysis to identify possible increases of anomaly rates during and after such disturbed days. We show that in the case of abundant series of anomalies on power lines, the anomaly rate increases significantly immediately (within 1 day) after the onset of geomagnetic storms. In the case of transformers, the increase of the anomaly rate is generally delayed by 2--3 days. We also find that transformers and some electric substations seem to be sensitive to a prolonged exposure to substorms, with a delayed increase of anomalies. Overall, we show that in the 5-day period following the commencement of geomagnetic activity there is an approximately 5--10\% increase in the recorded anomalies in the Czech power grid and thus this fraction of anomalies is probably related to an exposure to GICs.

          Related collections

          Author and article information

          Journal
          29 May 2020
          Article
          2005.14448
          6f57c8bd-54ba-475a-9e4d-a28d77141a0e

          http://creativecommons.org/licenses/by/4.0/

          History
          Custom metadata
          23 pages, 6 figures, 3 tables + online appendix. Accepted for publication in Journal of Space Weather and Space Climate
          physics.space-ph physics.soc-ph

          General physics,Space Physics
          General physics, Space Physics

          Comments

          Comment on this article