      Lessons From an Outbreak of Legionnaires’ Disease on a Hematology-Oncology Unit

      research-article

      Read this article at

      Bookmark
          There is no author summary for this article yet. Authors can add summaries to their articles on ScienceOpen to make them more accessible to a non-specialist audience.

          Abstract

          OBJECTIVES

          To define the scope of an outbreak of Legionnaires’ disease (LD), to identify the source, and to stop transmission.

          DESIGN AND SETTING

          Epidemiologic investigation of an LD outbreak among patients and a visitor exposed to a newly constructed hematology-oncology unit.

          METHODS

          An LD case was defined as radiographically confirmed pneumonia in a person with positive urinary antigen testing and/or respiratory culture for Legionella and exposure to the hematology-oncology unit after February 20, 2014. Cases were classified as definitely or probably healthcare-associated based on whether they were exposed to the unit for all or part of the incubation period (2–10 days). We conducted an environmental assessment and collected water samples for culture. Clinical and environmental isolates were compared by monoclonal antibody (MAb) and sequence-based typing.

          RESULTS

          Over a 12-week period, 10 cases were identified, including 6 definite and 4 probable cases. Environmental sampling revealed Legionella pneumophila serogroup 1 (Lp1) in the potable water at 9 of 10 unit sites (90%), including all patient rooms tested. The 3 clinical isolates were identical to environmental isolates from the unit (MAb2-positive, sequence type ST36). No cases occurred with exposure after the implementation of water restrictions followed by point-of-use filters.

          CONCLUSIONS

          Contamination of the unit’s potable water system with Lp1 strain ST36 was the likely source of this outbreak. Healthcare providers should routinely test patients who develop pneumonia at least 2 days after hospital admission for LD. A single case of LD that is definitely healthcare associated should prompt a full investigation.

          Related collections

          Most cited references30

          • Record: found
          • Abstract: found
          • Article: not found

          Addition of neuA, the gene encoding N-acylneuraminate cytidylyl transferase, increases the discriminatory ability of the consensus sequence-based scheme for typing Legionella pneumophila serogroup 1 strains.

          The standard sequence-based method for the typing of Legionella pneumophila serogroup 1 strains was extended by using the gspA and neuA alleles. The use of neuA as a seventh allele for typing significantly increased the index of discrimination calculated for a panel of unrelated strains (from 0.932 to 0.963) and subdivided some known large common complexes (e.g., 1,4,3,1,1,1). This modification to the standard method is proposed as the method of choice in the epidemiological investigation of L. pneumophila infections.
            Bookmark
            • Record: found
            • Abstract: found
            • Article: not found

            Trends in legionnaires disease, 1980-1998: declining mortality and new patterns of diagnosis.

            New diagnostic tests and empirical therapy for pneumonia may have important ramifications for the identification, treatment, and control of legionnaires disease (LD). To determine trends in the epidemiology of LD, we analyzed data for 1980-1998 from the passive surveillance system of the Centers for Disease Control and Prevention. During this time period, there were 6757 confirmed cases of LD (median annual number, 360 cases/year). Diagnosis by culture and by direct fluorescent antibody and serologic testing decreased significantly; diagnosis by urine antigen testing increased from 0% to 69%. The frequency of isolates other than Legionella pneumophila serogroup 1 (LP1) decreased from 38% to 4% (P=.003). The case-fatality rate decreased significantly, from 34% to 12% (P<.001) for all cases, from 46% to 14% (P<.0001) for nosocomial cases, and from 26% to 10% (P=.05) for community-acquired cases. LD-related mortality has decreased dramatically. The decrease in culture-based diagnosis limits the recognition of non-LP1 disease and impairs outbreak investigation, because fewer Legionella isolates are provided for further examination.
              Bookmark
              • Record: found
              • Abstract: found
              • Article: not found

              Vital Signs: Deficiencies in Environmental Control Identified in Outbreaks of Legionnaires' Disease - North America, 2000-2014.

              The number of reported cases of Legionnaires' disease, a severe pneumonia caused by the bacterium Legionella, is increasing in the United States. During 2000-2014, the rate of reported legionellosis cases increased from 0.42 to 1.62 per 100,000 persons; 4% of reported cases were outbreak-associated. Legionella is transmitted through aerosolization of contaminated water. A new industry standard for prevention of Legionella growth and transmission in water systems in buildings was published in 2015. CDC investigated outbreaks of Legionnaires' disease to identify gaps in building water system maintenance and guide prevention efforts.
                Bookmark

                Author and article information

                Journal
                8804099
                4791
                Infect Control Hosp Epidemiol
                Infect Control Hosp Epidemiol
                Infection control and hospital epidemiology
                0899-823X
                1559-6834
                31 March 2018
                06 December 2016
                March 2017
                06 April 2018
                : 38
                : 3
                : 306-313
                Affiliations
                [1 ]Epidemic Intelligence Service Program, Atlanta, Georgia
                [2 ]Centers for Disease Control and Prevention, Atlanta, Georgia
                [3 ]Alabama Department of Public Health, Montgomery, Alabama
                [4 ]Jefferson County Department of Health, Birmingham, Alabama
                Author notes
                Address correspondence to Louise K. Francois Watkins, 1600 Clifton Rd. NE, Mailstop C-09, Atlanta, GA 30329 ( hvu9@ 123456cdc.gov )
                Article
                HHSPA954914
                10.1017/ice.2016.281
                5887123
                27919312
                b9e468d4-db1e-483d-b7ed-10aeb23c9b51

                This is an Open Access article, distributed under the terms of the Creative Commons Attribution licence ( http://creativecommons.org/licenses/by/4.0/), which permits unrestricted re-use, distribution, and reproduction in any medium, provided the original work is properly cited.

                History
                Categories
                Article

                Comments

                Comment on this article